Number and cross- section of power + grounding conductors |
Power conductor stranding | Grounding/Ground check conductor stranding | Nominal insulation thickness | Nominal jacket thickness | Approximate overall diameter | Maximum conductor resistance at 200C | Ampacity at ambient temperature 300C |
Approximate weight of cable |
mm2 | N x mm | N x mm | mm | mm | mm | Ω/km | A | kg/km |
6/10 kV | ||||||||
3x50+2x16+1x10 | 364x0.4 | 116x0.4/74x0.4 | 3.4 | 5.5 | 54.0 | 0.393 | 202 | 4307 |
3x70+2x35+1x10 | 514x0.4 | 254x0.4/74x0.4 | 3.4 | 5.5 | 54.8 | 0.277 | 250 | 5534 |
3x95+2x35+1x16 | 684x0.4 | 254x0.4/116x0.4 | 3.4 | 5.5 | 62.6 | 0.210 | 301 | 6901 |
3x120+2x50+1x10 | 870x0.4 | 364x0.4/74x0.4 | 3.4 | 5.5 | 66.3 | 0.164 | 352 | 7467 |
3x185+2x70+1x35 | 1325x0.4 | 514x0.4/254x0.4 | 3.4 | 5.5 | 75.6 | 0.108 | 461 | 11100 |
8.7/15 kV | ||||||||
3x50+2x16+1x10 | 364x0.4 | 116x0.4/74x0.4 | 4.5 | 5.5 | 60.3 | 0.393 | 215 | 4900 |
3x70+2x35+1x10 | 514x0.4 | 254x0.4/74x0.4 | 4.5 | 5.5 | 63.2 | 0.277 | 265 | 6100 |
3x95+2x35+1x16 | 684x0.4 | 254x0.4/116x0.4 | 4.5 | 5.5 | 68.2 | 0.210 | 319 | 7100 |
3x120+2x50+1x10 | 870x0.4 | 364x0.4/74x0.4 | 4.5 | 5.5 | 72.2 | 0.164 | 371 | 8400 |
3x185+2x70+1x35 | 1325x0.4 | 514x0.4/254x0.4 | 4.5 | 5.5 | 76.7 | 0.108 | 488 | 12100 |
14/25 kV | ||||||||
3x50+2x16+1x10 | 364x0.4 | 116x0.4/74x0.4 | 6.8 | 5.5 | 65.1 | 0.393 | 215 | 6800 |
3x70+2x35+1x10 | 514x0.4 | 254x0.4/74x0.4 | 6.8 | 5.5 | 69.7 | 0.277 | 265 | 8000 |
3x95+2x35+1x16 | 684x0.4 | 254x0.4/116x0.4 | 6.8 | 5.5 | 75.3 | 0.210 | 319 | 9000 |
3x120+2x50+1x10 | 870x0.4 | 364x0.4/74x0.4 | 6.8 | 5.5 | 78.3 | 0.164 | 371 | 9400 |
3x185+2x70+1x35 | 1325x0.4 | 514x0.4/254x0.4 | 6.8 | 5.5 | 86.3 | 0.108 | 488 | 14000 |